CalcHub

Circuit Breaker Size Calculator

A properly sized circuit breaker protects your wiring from overload and fire. This calculator determines the correct breaker size based on your load type, current draw, and NEC requirements.

Enter Your Measurements

Results

Enter your measurements to see results

How to Use This Calculator

  1. Enter the total load in watts.
  2. Select the circuit voltage.
  3. Indicate if the load runs continuously (3+ hours).
  4. Review the recommended breaker and wire size.

How Breaker Size Calculation Works

The calculator divides watts by voltage to get amps, applies the NEC 125% continuous load factor if applicable, then rounds up to the next standard breaker size per NEC 240.6. It also recommends the minimum wire gauge that matches the breaker rating. The breaker must never exceed the wire's ampacity — they are sized as a matched pair.

Formula

Load amps = Watts ÷ Volts. Required capacity = Load amps × 1.25 (if continuous). Round up to next standard breaker size (15, 20, 25, 30, 40, 50, 60, 70, 80, 100A).

Frequently Asked Questions

What size breaker for a 1,500-watt heater?
1,500W ÷ 120V = 12.5A. Since heaters are continuous loads: 12.5 × 1.25 = 15.6A. Round up to a 20A breaker with 12 AWG wire.
Can I put a larger breaker to stop tripping?
No — this is a code violation and fire hazard. If a breaker trips frequently, the circuit is overloaded. Add a new circuit or reduce the load.
What size breaker for an EV charger?
Most Level 2 chargers draw 32–48 amps. At 32A continuous: 32 × 1.25 = 40A breaker with 8 AWG wire. At 48A: 48 × 1.25 = 60A breaker with 6 AWG wire.